United Petroleum Services FZE

Circuit Breaker>>Mould Case Circuit Breaker>>AM1 Series


1. Application
AM1 series moulded case circuit breaker is one of products developed and manufactured byadopting international advanced technology. It is supplied with rated insulating voltage 800Vand used for circuit of A.C. 50Hz, rated operating voltage AC 400V (or below), rated operatingcurrent up to 800A for infrequent changing over and starting of the motors.The products con-forms to IEC60947-2 standard.
2. Main Technical Specification

Table1

Type
Rated
current (A)
Pole
Ratedinsui-atingvolt-age(V)
Rated
operat-ingvolt-age(V)
Arcing-
over
distance
(mm)
Ultimate
short
circuit
breaking
capacity
(KA)
Servies
short
circuit
breaking
capacity
(KA)
AM1-63L
(6),10
16,20
25 ,32
40,50
63
3, 4
500V
400V
0
25
18
AM1-63M
0
50
35
AM1-100L
(10),16
20,25
32,40
50,63
80,100
800V
0(≤50)
35
22
AM1-100M
0(≤50)
50
35
AM1-100H
0(≤50)
85
50
AM1-225L
100,125
160,180
200,225
≤50
35
22
AM1-225M
≤50
50
35
AM1-225H
≤50
85
50
AM1-400L
225,250
315,350
400
≤50
50
35
AM1-400M
≤100
65
42
AM1-630L
400,500
630
≤100
50
35
AM1-630M
≤100
65
42
AM1-630H
≤100
100
65
AM1-800M
630,700
800
3
≤100
75
50
AM1-800H
≤100
100
65
AM1-1250M
1000,1250
≤100
100
65
AM1-1250H
≤100
125
5

Note: 6A no thermal protection The N-pole of four-poles breaker is sifed at the right side of the product has four types: Type A: No current trip-lease on N pole which making all the time, not closing and opening with the otherthree poles. Type B: No current trip-release on N pole which closing and opening with the other poles. Type C: With current trip-release which closing and opening with the other three poles. Type D: With current frip-release which making all the time not closing and opening with the other threepoles.

3. Protection Characteristic
The thermodynamic release of a circuit breaker provides the feature of inverse time-delay,while the magnetic release is the instantaneous operation as shown on table 2(distribution cir-cuit breaker) and table 3 (motor protection circuit breaker).
Table2
Rated current ofrelease (A)

Thermodynamic release

( ambient temp )

Operationalcurrent ofmagneticrelease (A)
1.05In(cold state)
Inoperative time(h)
1.30In (heat state)
Operative time(h)
10≤In≤63
≥1
< 1
10In±20%
225≤In≤630
≥2
< 2
100≤In≤800
≥2
< 2
5In±20%

Table3
Rated current ofrelease (A)
Thermodynamic release( ambient temp )
Operationalcurrent ofmagneticrelease (A)

1.0In

(cold state)
Inoperative time(h)

1.20In(heat state)
Operative time (h)
1.50In(heat state)
Operative time (h)
7.2In(cold state)
Operative time(h)
10≤In≤225
≥2
<2
≤4min
≤8min
4s< Tp ≤10s
6s< Tp ≤20s
12In±20%