United Petroleum Services FZE

Circuit Breaker>>Mould Case Circuit Breaker>>AM2 Series


1.Application
AM2 series moulded case circuit breaker is one of breaker which adopts international ad-vanced design, manufacture technology to develop. The rated insulating voltage is 750V, suit-able for AC 50Hz(60Hz),rated working voltage 690V or below, rated working current is 12.5A to1250A of circuit and used in distributing electric energy, and non-frequent breaking in the nor-mal conditions , protecting the current& equipment from overload&under voltage, circuit breakerwith rated frame current 400A or below,can be used in mousecage motor's non-frequent start,breaking during working, protecting motor from overload, short circuit&undervoltage,the prod-uct conforms to IEC60947-2 standard.

2.Main Technical Specifications

Type
Pole number
Rated insulating voltage(V)
Rated operating voltage(V)
Rated ultimate short circuit breaking capacity Icu (KA) at 380/415V
Rated servies short circuit breaking capacity Ics at 380/415V(KA)
Operation performance
ON
OFF
AM2-100N
3, 4 pole
750
690 and below
25
25
1500
8500
AM2-100H
70
70
AM2-100L
150
150
AM2-160N
36
36
1000
7000
AM2-160H
70
70
AM2-160L
150
150
AM2-250N
36
36
1000
7000
AM2-250H
70
70
AM2-250L
150
150
AM2-400N
45
45
1000
4000
AM2-400H
70
70
AM2-400L
150
150
AM2-630N
45
45
1000
4000
AM2-630H
70
70
AM2-630L
150
150
AM2-1250N
3 pole
50
37.5
1000
4000
AM2-1600N
50
37.5
Note:1. The N-pole breaker has no protection which closing and opening with the other three poles. 2. The type of thermal magnetic for AM2-400/630 has no four poles.

3 Trip units main technical parameter
Thermal magnetic release

 

Type
Rated currentIn(A)
Note
AM2-100
12.5,16,20,25,32,40,50,63,80,100

Tadjustable (0.8~1In)M

adjustable (5~10In)

AM2-160
16,20,25,32,40,50,63,80,100,125,160
AM2-250
160,180,200,225,250
AM2-400
315,350,400
AM2-630
400,500,630
AM2-1250
800,1000,1250
Tadjustable (0.8~1In)M fixed
AM2-1600
1000,1250,1600

 

Electronic release
AM2 22SE: protection of low-voltage distribution networks for AM2-100\160\250

1. Overload protection with adjustable threshold
2. Short-circuit protection with adjustable threshold
3. Load indication : light at 90% of Ir setting threshold;
Flashing at 105% or more of Ir setting threshold

Type
Rated current In(A)
Note
AM2-100
40,100
Ir=0.4~1×In(adjustable 48 setting)
Tripping between 1.05~.3×Ir (IEC60947-2)
(Long-time overload protection)
Im=2-3-4-5-6-7-8-10×Ir
(Short-circuit protection)
AM2-160
40,100,160
AM2-250
40,100,160,250


AM2 22ME: protection of motor for AM2-100\160\250

 

 

1. Overload protection with adjustable threshold, as defined by IEC60947-4 (2) tripping class 10
2. Short-circuit protection with fixed threshold (13xIr)
3. phase failure protection (tripping time delay between 3.5s-6s)
4. Load indication : dark less than 105% of Ir setting threshold;
Flashing at 105% or more of Ir setting threshold


Type Rated current In(A) Note
AM2-100 40,50,80,100

Ir=0.6-0.63-0.67-0.71-0.75-0.80-0.85-0.90

-0.95-1×In

AM2-160 40,50,80,100,150
AM2-250 40,50,80,100,150,220


AM2 23SE: protection of low-voltage distribution networks for AM2-400\630

 

 

1. Overload protection with adjustable threshold
2. Short-circuit protection with adjustable threshold
3. Load indication : light at 90% of Ir setting threshold;
Flashing at 105% or more of Ir setting threshold


Type
Rated current In(A)
Note
AM2-400
400
Ir=0.4~1×In(adjustable 48 setting)
Tripping between 1.05~1.3×Ir (IEC60947-2)
(Long-time overload protection)
Im=2-3-4-5-6-7-8-10×Ir
(Short-circuit protection)
AM2-630
630

AM2 53UE: protection of low-voltage distribution networks for AM2-400\630

 

 

1. Overload protection with adjustable threshold, as defined by IEC60947-2
2. Short-circuit protection with adjustable threshold
3. Instantaneous short-circuit protection
4. Earth fault protection with adjustable threshold
5. Load indication : light at 90% of Ir setting threshold;
Flashing more than Ir setting threshold
6. Fault indication
LEDs indicates the type of fault that caused tripping
Overload (LT protection) or abnormal component temperature (>Ir);
Short-circuit (ST or instantaneous protection)( >Im);
Earth fault (if earth fault protection option is present)(Ig);
Microprocessor malfunction (both (>Ir) and ( >Im) LEDs go on ,plus the (Ig) LEDs if earth fault protection option is present )
Battery powered. Spare battery are supplied in an adapter box. When a fault occurs , the LED indicating the type of fault ,lights for about 10 minutes . The information is however stored in memory . The LED can be illuminated by pressing the test pushbutton. The LED automatically goes off and the memory is cleared when the circuit breaker is reset .


Type
Rated current In(A)
Note
AM2-400
400

Ir=0.4~1×In(adjustable 48 setting)
Tripping between 1.05~1.3×Ir (IEC60947-2)
at 6×Ir Trip time: 1s, 2s, 4s, 8s, 16s(adjustable)
(Long-time overload protection)
Isd=1.5-2-3-4-5-6-7-8-10×Ir
Trip time: 0s, 0.1s, 0.2s, 0.3s adjustable+I2t
(Short-circuit short time delay protection)
Ii=1.5-2-3-4-6-7-8-10-11×Ir
(Instantaneous short-circuit protection)
Ig=0.1-0.2-0.3-0.4-0.5-0.6-0.7-0.8-1×Ir
Trip time: 0.1s, 0.2s, 0.3s, 0.4s adjustable+I2t
(Earth fault protection) (If option is present)

AM2-630
630


AM2 43ME: protection of motor for AM2-400\630

 

 

1. Overload protection with adjustable threshold, as defined by IEC60947-4 (2) tripping class 10A,10 and 20
2. Short-circuit protection with adjustable threshold (6...13xIr)
3. Phase failure protection (built-in electronic release: operates unbalanced single-phase currentat 40% and more than )(tripping time delay 4s¡À10%),as defined by IEC60947-4.1
4. Load indication : Flashing more than Ir setting threshold
5. Fault indication
LEDs indicates the type of fault that caused tripping
Overload (LT protection) or abnormal component temperature (>Ir);
Short-circuit (ST or instantaneous protection)( >Im);
Phase failure (right LED);
Microprocessor malfunction ( (>Ir) ( >Im) and phase failure LEDs all go on )
Battery powered. Spare battery are supplied in an adapter box. When a fault occurs ,the LEDindicating the type of fault ,lights for about 10 minutes . The information is however stored inmemory . The LED can be illuminated by pressing the test pushbutton. The LED automaticallygoes off and the memory is cleared when the circuit breaker is reset .

Type
Rated current In(A)
Note
AM2-400
400

Ir=0.4~1×In(adjustable 48 setting)
Trip degree: class 10A, 10,20(IEC60947-4)
(Long-time overload protection)
Im=6-7-8-9-10-11-12-13×Ir
(Short-circuit protection)