Circuit Breaker>>Mould Case Circuit Breaker>>AM3 Series


1.Application
AM3 series moulded case circuit breaker , it's applicable circuit of AC 50Hz(or 60Hz),ratedinsulation voltage 690V(AM3-125 500V),rated operating voltage AC 690V or below ,rated oper-ating current 12.5-1600A, for distribute energy of electric and infrequent making and breakingcircuit in normal condition. The circuit-breakers are provided with the function of the protectionagainst overload and short circuit and under-voltage. The circuit breakers comply with standardof IEC60947-2.The circuit-breakers are double insulating (Inm=250A or above), the controlcircuit of the accessories is set apart with the main circuit , and doesn't need to open the coverof the circuit-breaker when install the accessories.

2. Specification

Type
Pole
Rated insulating voltage(V)
Rated operating voltage(V)
Ultimate short circuitbreaking capacity Icu(KA)
Rated short-circuitserrice breakingcapocity Ics(%icu)

AC380V

(400)

AC660V

(690)

AM3-125L
1,2,3,4
500
500
25
-
50%
AM3-160L
3,4
690
690 and below
35
8
75%
AM3-160M
50
10
75%
AM3-250L
800
35
14
100%
AM3-250M
65
18
75%
AM3-250H
85
20
75%
AM3-400L
35
18
100%
AM3-400M
65
22
100%
AM3-400H
100
30
75%
AM3-630L
35
20
100%
AM3-630M
50
22
100%
AM3-630H
65
25
100%
AM3-800L
35
20
100%
AM3-800M
50
22
100%
AM3-800H
65
25
100%
AM3-1250/1600L
3
50
20
100%



3. Trip units main technical parameter

 

 

 

Type
Thermal magnetic release
Electronic release
Rated currentIn(A)
Note

Rated

current In(A)

Note
AM3-125

12.5,16,20,

25,32,40,50,

63,80,100,125

T fixedM fixed
-
AM3-160

16,20,25,32,

40,50,63,80,

100,125,160

T adjustable (0.7~1In)M fixed
-
AM3-250

100,125,160,

180,225,250

T adjustable (0.7~1In)M fixed
-
AM3-400

225,250,315,

350,400

T fixed or adjustable (0.7~1In)M fixed
320,400
I1=0.4...1×In AM3 PR211(L-LI)
I1=0.4...1×In AM3 PR212(LSI-LSIG)
Tripping between 1.05...1.3×I1(IEC60947-2) I2t=constant(Long-time overload protection)
I2=1-2-3-4-6-8-10×In
t2=0.05s,0.1s,0.25s,0.5s adjustable(Short-circuit short time delay protection)
I3=1.5-2-4-6-8-10-12×In(Instantaneous short-circuit protection)
I4=0.2-0.3-0.4-0.6-0.8-0.9-1×In
t4= 0.1s, 0.2s, 0.4s, 0.8s adjustable(Earth fault protection)
AM3-630
400,500,630
T fixedM fixed
630
AM3-800
630,700,800
T fixedM fixed
800
AM3-1250
-
-

800,

1000,

1250

AM3-1600
-
-

1000,

1250,

1600


Note: T-thermal M-magnetic L-long time S-short time relay I-instantaneous G-earth fault AM3-125/160 In=12.5,16,20,32,40 magnetic protection that is fixed at 500A.