United Petroleum Services FZE

Circuit Breaker>>Miniature Circuit Breaker>>DZ51-63 Series

 

1.Application

DZ51-63 is mainly suitable for overload and short circuit protection. It is especially used forillumination and distribution in industry and commerce, etc. It has pleasing outlook & high break-ing capacity, reliable performance, high inflammable resistance and shock resistance for longservice life. It is within the circuit of AC 50/60Hz, rated voltage of single pole up to 240V, two,three or four poles up to 415V. It can also be used for an unfrequent change over of the circuitand illumination under normal condition.It conforms with the standards of IEC60898.

2.Main Technical Parameter

 

Type
DZ51-63
Pole
1P
2P, 3P, 4P
Rated current (A)
1,2,3,4,6,10,16,20,25,32,40,50,63
Rated voltage(V)
230
400
Type of instantaneous release
B,C,D
Rated short circuit breaking capacity Icn(KA)
10
Life (times)
1-32A
Electric life
8000
Mechanical life
6000
Operation frequency
240 times per hour
40-63A
Electric life
8000
Mechanical life
6000
Operation frequency
120 times per hour

 

3.Applicable conducting wire

 

Rated current(A)
Nominal cross section of wire mm2
1-6A
1
10A
1.5
16,20A
2.5
25A
4
32A
6
40,50A
10
63A
16

 

4.The over-current protection property

 

Ambient Temperature
Initial Status
Test Current
Expected Result
Expected Result
Note
30±2oC
Cold position
1.13In
t≥1h
Non-release
-
Carried out immediately after previous test
1.45In
t<1h
Release
-
Cold position
2.55In
1s<t<60s
(In≤32A)
Release
Current smoothly rises to specified value within 5s
Cold position
2.55In
1s<t<120s
(In>32A)
Release
-5~+40oC
Cold position
3In
t≥0.1s
Non-release
Type B
Cold position
5In
t<0.1s
Release
Type B
Cold position
5In
t≥0.1s
Non-release
Type C
Cold position
10In
t<0.1s
Release
Type C
Cold position
10In
t≥0.1s
Non-release
Type D
Cold position
20In
t<0.1s
Release
Type D