United Petroleum Services FZE

Fuses>>NT Series


1.Application


NT low voltage H.R.C. fuse features light in weight, small in size, low in power loss and high in breaking capacity. This product has been widely used in overload and short circuit protection of electric installation. This product conforms to IEC 60269 standards with all of the rating at the world advanced level.

 

2. Specification

 

Size Fuse Base
Rated current (A) Rated voltage (V) Rated power loss (W) Weight (kg) Type Rated current (A) Weight (kg)
NT00C 2 500, 600 0,41 0,15 01 160 0,2
4 0,62
6 0,81
10 1,08
16 1,60
20 1,81
25 2,31
32 3,07
36 3,17
40 4,05
50 4,25
63 4,70
80 5,70
100 7
NT00 4 500, 600 0,67 0,15 02 160 0,2
6 0,89
10 1,14
16 1,65
20 1,94
25 2,50
32 3,32
36 3,56
40 4,30
50 4,50
63 4,60
80 6
100 7,30
125 500 7,60
160 9,60
NT0 6 500, 600 1,03 0,2 03 160 0,32
10 1,42
16 2,45
20 2,56
25 2,7
32 3,74
35 4,3
40 4,7
50 5,5
63 6,9
80 7,6
100 8,9
125 500 10,1
160 15,2
NT1 80 500, 600 6,2 0,36 04 250 0,8
100 7,5
125 10,2
160 13
200 15,2
224 500 16,8
250 18,3
NT2 125 500, 600 9 0,65 05 400 1,2
160 11,5
200 15
224 16,6
250 18,4
300 21
315 19,2
355 24,5
400 26
NT3 315 500, 600 21,7 0,85 06 630 1,5
355 22,7
400 26,8
425 28,9
500 500 32
630 40,3
NT4 800 380 62 1,95 07 1000 3,45
1000 75