United Petroleum Services FZE

Contactor>>AC Contactor>>CJX7 Series


1.Application

 

CJX7(A)-9~185 AC contactor (hereafter refer to as contactor) is mainly used in power system with AC50Hz (or 60Hz), therated working voltage up to 660V,under the applicatio category of AC-3,when the rated working voltage 380V,the rated operating current to 185A electrical, for the long-distance range making and breaking the electric circuit, and combines the electromagnetism starter with the suitabe thrmal ovetload relay or the electronic protector to protect against the possible overload elctric circuit during operation (running).

 

2.Specification

 

Type
Frame code
Rated insulation voltage Ui V
Convensional free air heat current Ith
AC-3 rated operating current Ie A
AC-3 control the max. power KW of generator
220V
380V
660V
220V
380V
660V
CJX7(A)-9
16
100
25
9
9
7
2.2
4
5.5
CJX7(A)-12
27
12
12
9
3
5.5
7.5
CJX7(A)-16
30
17
17
10
4
7.5
9
CJX7(A)-26
26
45
26
26
17
6.5
11
15
CJX7(A)-30
40
55
32
32
21
9
15
18.5
CJX7(A)-40
60
37
37
25
11
18.5
22
CJX7(A)-50
75
100
50
50
35
15
22
30
CJX7(A)-63
115
65
65
43
18.5
30
37
CJX7(A)-75
125
75
75
46
22
37
40
CJX7(A)-95
110
145
96
96
65
25
45
55
CJX7(A)-110
160
110
110
82
30
55
75
CJX7(A)-145
250
145
145
100
43
75
95
CJX7(A)-185
275
185
185
130
51
90
100