Contactor>>AC Contactor>>MC1-D Series
Specification
Type | MC1-D 09...18 T20&T25 |
MC1-D 25...38 T32&T40 |
MC1-D 40 |
MC1-D 50...95 |
MC1-D115&MC1-D150 |
|
Rated insulation voltage (Ui) | Conforming to IEC 947-4-1,overvoltage category III,degree of pollution:3 |
690V |
690V |
690V |
690V |
690V |
Rated impulse withstand voltage(Uimp) | Conforming to IEC947 |
6kV |
6kV |
8kV |
8kV |
8kV |
Conforming to standards | IEC947-1,947-4-1,EN 60947-1,60947-4-1 |
|||||
Degree of protection(1) | Power connection |
Protection against direct finger contact IP2X |
||||
Front face only | Coil connection |
Protection against direct finger contact IP 2X(except MC1-D40...80 |
||||
Protective treatment | Conforming to IEC68 |
"TH" |
||||
Ambient air temperature | Storage |
-60...+80 ℃ |
||||
Around the device | Operation |
-5...+60℃ |
||||
Permissible |
-40...+70℃,for operation at Uc |
|||||
Maximum operating altitude | Without derating |
3000m |
||||
Operating position | Without derating |
±30°possible, in relation to normal vertical mounting plane |
||||
Flame resistance | Conforming to IEC 695-2-1 |
960℃ |
||||
Shock resistance(2) | Contactor open |
10gn |
8gn |
8gn |
8gn |
6gn |
1/2 sine wave=11ms | Contactor closed |
15gn |
15gn |
10gn |
10gn |
15gn |
Vibration resistance(2) | Contactor open |
2gn |
2gn |
2gn |
2gn |
2gn |
5...300Hz | Contactor closed |
4gn |
4gn |
4gn |
3gn |
4gn |
(1), Protection ensured for the connection cross-sections shown on the nex t page and for connection via cable
(2), In the least favourable direction,without change of contact state(coil supplied at Ue).
Type of contactor | MC1-D- |
D40 |
D50 |
D65 |
D80 |
D95 |
|||||
Rated operational current(te) (Ue≤440V) |
In AC-3,θ=60℃ |
A |
40 |
50 |
65 |
80 |
95 |
||||
In AC-1,θ=60℃ |
A |
60 |
80 |
80 |
125 |
125 |
|||||
Rated operational voltage(Ue) | Up to |
V |
1000 |
1000 |
1000 |
1000 |
1000 |
||||
Frequency limits | Of the operating current |
Hz |
25...400 |
25...400 |
25...400 |
25...400 |
25...400 |
||||
Conventional thermal current(1th) | θ≤60℃ |
A |
60 |
80 |
80 |
125 |
125 |
||||
Rated making capacity(440V) | Conforming to IEC 947 |
800 |
900 |
1000 |
1100 |
1100 |
|||||
Rated breaking capacity(440V) | Conforming to IEC 947 |
800 |
900 |
1000 |
1100 |
1100 |
|||||
Permissible short-time rating No current flowing for preceding 15 minutes at θ≤40℃ |
For 1 s |
A |
720 |
810 |
900 |
990 |
1100 |
||||
For 10 s |
A |
320 |
400 |
520 |
640 |
800 |
|||||
For 1min |
A |
165 |
208 |
260 |
320 |
400 |
|||||
For 10 min |
A |
72 |
84 |
110 |
135 |
135 |
|||||
Protection by fuse against short-circuits(U≤690V) |
Without thermal type 1 |
A |
80 |
100 |
160 |
200 |
200 |
||||
Overload relay,fuse gG type 1 |
A |
80 |
100 |
125 |
160 |
160 |
|||||
With thermal overload relay |
A |
See pages 245 14/2 and 245 14/3,for aM or gG fuse ratings corresponding to the associated thermal overload relay |