Contactor>>Other contactor>>MS2-252 Series contactors
Features
Designed for central air conditioning and heating equipment.
1.Any position mounting
2.Interchangeable mounting plate
3.Low wattage coil
4.Double break contacts ensure positive make and break.
Specifications
Insulating material |
Contact block and carrier are high quality electrical-grade thermosetting resin |
Temperature range |
-40°F to 150°F |
Mechanical life (no load) |
Conforms to UL and ARI specifications |
Electricl life |
Conforms to UL and ARI specifications |
Weight (approximate) |
16 oz |
Coils Frequency |
50/60Hz |
Coil insulation |
Class B(130℃ ) 24 through 208/240 Volts AC |
Termination |
Pressure connector and double 1/4 Q.C |
Operate |
85% of nominal coil voltage; 110% maximum safe operate |
Duty cycle |
Continuous |
|
Coil data -25 and 30Amp,600volt three pole normally open (3.P.N.O) |
Steveco Number
25 Amp 30Amp |
Voltage AC |
Ress DC OHMS |
Current MA |
Nominal VA |
Max. inrush |
MC2-160 MC2-163 |
24 |
9.2 |
187 |
4.5 |
52 |
MC2-161 MC2-164 |
120 |
180 |
37 |
4.5 |
52 |
MC2-162 MC2-165 |
208/240 |
720 |
19 |
4.5 |
52 |
|
Contact ratings --25 and 30Amp,600volt three pole normally open (3.P.N.O) |
Type |
Voltage |
277VAC |
480VAC |
600VAC |
MC2-160 thru MC2-162 |
Full load
Lock rotor
Resistive |
25 A. |
25 A. |
25 A. |
150 A. |
125 A. |
100 A. |
40 A. |
40 A. |
40 A. |
MC2-163 thru MC2-165 |
Full load
Lock rotor
Resistive |
30 A. |
30 A. |
30 A. |
180 A. |
150 A. |
120 A. |
50 A. |
50 A. |
50 A. |
|
Coil data -40 Amp ,600 volt three pole normally open (3.P.N.O) |
Steveco Number
40 Amp |
Coil Voltage AC
(60Hz) |
Ress DC OHMS |
Current MA |
Nominal VA |
Max. inrush VA |
MC2-170 |
24 |
7.2 |
187 |
4.5 |
52 |
MC2-171 |
120 |
180 |
37 |
4.5 |
52 |
MC2-172 |
208/240 |
720 |
19 |
4.5 |
52 |
|
Contact ratings -40 Amp ,600 volt three pole normally open (3.P.N.O) |
Type |
Voltage |
277VAC |
480VAC |
600VAC |
MC2-170 thru MC2-172 |
Full load
Lock rotor
Resistive |
40 A. |
40 A. |
40 A. |
240 A. |
200 A. |
160 A. |
50 A. |
50 A. |
50 A. |
|