United Petroleum Services FZE

Relay>>JRS5 Series Thermal Relay

 

1.Application

JRS5 thermal relay is suitable for overload protection of AC motor operated on 8-houres dutyor uninterupted duty. The overload protected AC motor with frequency 50Hz, voltage up to660V, current up to 105A. Several functions provided by these relays are: phase-failure protection,temperature compensation, ON/OFF indication and manual/automatic reset. The product con-forms to IEC60947-4-1 stardand.

 

2. Motion Characteristic: Three-phase Balance Motion Time

 

No
Times of thesetting current
Motion time
Start condition
Ambienttemperature
1
1.05
>2h
Cold state
20±5˚C
2
1.2
<2h
Heat state
(Following the No.1 test)
3
1.5
<4min
4
7.2
10A
2s < Tp≤10s
≤63A
Cold state
10
4s < Tp ≤10s
>63A

3. Phase-losing Motion Characteristic
No
Times of the setting current
Motiontime
Start condition
Ambient temperature
Any two phases
Another phase
1
1.0
0.9
>2h
Cold state
20±5˚C
2
1.15
0
< 2h
Heat state(Following the No.1 test)

4. Specification

Type
Setting range(A)
Forcontactor
JRS5-12/Z
0.2~0.28
S-K10
S-K11
S-K12
S-K18
S-K20
S-K21
0.4~0.6
0.55~0.85
0.7~1.1
1~1.6
1.4~2
1.7~2.5
2~3
2.8~4.4
4~6
5.2~8
7~11
9~13
JRS5-20/F
0.2~0.28
S-K18
S-K20
S-K21
S-K25
S-K35
0.28~0.42
0.4~0.6
0.55~0.85
0.7~1.1
1~1.6
1.4~2
1.7~2.5
JRS5-20/F
2~3
S-K18
S-K20
S-K21
S-K25
S-K35
2.8~4.4
4~6
5.2~8
7~11
9~13
12~18
16~22
18~26
24~34
30~40
JRS5-60/F
12~18
S-K50
S-K65
S-K80
S-K95
16~22
18~26
24~34
30~40
34~50
43~65
54~80
65~93
85~105