United Petroleum Services FZE

Relay>>JR56 Series Thermal Relay

 

1.Application

JR56 series thermal relay is used in the circuit of 50/60Hz, rated insulation voltage 660V,rated current 0.3-95A for protecting the phase break when the electric motor is overloaded. Therelay has different mechanism and temperature compensation. It can be plugged in CJX3 seriesAC contactor. The product conforms to IEC60947-4-1 stardand.

 

2.Motion Characteristic: Three-phase Balance Motion Time

 

No Times of the setting current Motion time Start conidition Ambient temperature
1 1.05 >2h Cold state 20±5oC
2 1.2 <2h Heat state (Following the No.1 test)
3 1.5 <4min
4 7.2 10A 2s<Tp≤10s ≤63A Cold state

 

 

3.Phase-losing Motion Characteristic

 

No Times the setting current Motion time Start condition Ambient temperature
Any two phases Another phase
1 1.0 0.9 >2h Cold state 20±5oC
2 1.15 0 <2h Heat state(Following the No.1 test)

 

4.Specification

 

Type Setting range (A) For contactor
JR56-20 0.3~0.5 CJX3-10

CJX3-11

CJX3-12

CJX3-16

CJX3-18

CJX3-19

CJX3-25
0.6~1
1~1.6
1.5~2.5
2~3
3~5
4~6
4.8~8

 

Type Setting range (A) For contactor
JR56-20 7.5~12
12~18
20~28
JR56-63 24~34 CJX3-35

CJX3-50

CJX3-65

CJX3-80
25~40
28~62
48~80
60~95